ISSN ONLINE(2278-8875) PRINT (2320-3765)

All submissions of the EM system will be redirected to Online Manuscript Submission System. Authors are requested to submit articles directly to Online Manuscript Submission System of respective journal.

Fault Detection, Isolation And Identification Of Fault Location In Low-Voltage Dc Ring Bus Microgrid System

S.Vimalraj1, Dr.P.Somasundaram2
  1. PG Student [PSE], Dept. of EEE, College of Engineering, Guindy, Anna University, Chennai, India
  2. Associate Professor, Power System Engg. Division, College of Engineering, Guindy, Anna University, Chennai, India
Related article at Pubmed, Scholar Google

Visit for more related articles at International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering

Abstract

Unlike traditional AC distribution systems, protection has been challenging for DC systems. Multiterminal DC power systems do not have the years of practical experience and standards that AC power systems have. Also, the current power electronic devices cannot survive or sustain high magnitude faults. Converters will shut down to protect themselves under faulted conditions. This makes locating faults in DC system difficult and causes the DC bus to de-energize. A fault protection algorithm for low-voltage DC-Ring bus microgrid system is presented in this paper in order to resolve the above issues. The main objective of the proposed method is to detect and isolate faults in the dc ring bus system without de-energizing the entire system and identifying the fault location. A non-iterative fault-location technique using a probe power is also presented in this paper. This probe power can also be used for a pilot test before main CB reclosing to avoid system issues that can be expected when the reclosing fails due to a permanent fault. The proposed concepts have been verified by OrCAD/Pspice simulations

Keywords

DC distribution, fault protection, fault location, microgrid, power system protection

INTRODUCTION

Recently, many distributed power systems have been researched and developed, especially to meet the demand for high penetration of renewable energy resources, such as wind turbines and photovoltaic systems. The distributed power systems have advantages, such as the capacity relief of transmission and distribution, better operational and economical generation efficiency, improved reliability, eco-friendliness, and higher power quality [1]. The microgrid system is a small-scale distributed power system consisting of distributed energy sources and loads, and it can be readily integrated with the renewable energy sources [2]. Due to the distributed nature of the microgrid approach, the connection to the central dispatch can be removed or minimized so that the power quality to sensitive loads can be enhanced. Generally, they have two operation modes: stand-alone (islanded) mode and grid-connected mode.
Microgrid systems can be divided into ac-bus and dc-bus systems, based on the bus to which the component systems are connected. The advantage of the ac-bus-based microgrids is that the existing ac power grid technologies are readily applicable. However, problems with the ac grid issues, including synchronization, reactive power control, and bus stability, still persist. DC ring bus-based systems can become a feasible solution because microgrids are small, localized systems where the transmission loss is negligible. A conceptual diagram of the dc-bus microgrid is shown in Fig. 1.While the advantages of dc microgrids are considerable, the protection of dc distribution systems has posed many challenges, such as autonomously locating a fault within a microgrid, breaking a dc arc, dc protective equipment, and certainly the lack of standards, guidelines, and experience [3]. This paper presents a fault detection, isolation and identification of fault location scheme for a low-voltage dc ring bus microgrid system.
The main objectives of the proposed scheme are to detect the fault in a bus segment between devices and then to isolate the faulted section so that the system continues to operate without disabling the entire system. Also proposed is a noniterative, deterministic fault location technique using a probe power unit. The information on fault location is extracted from the probe current.
image
The probe power unit can also be used for a pilot test to determine whether the fault is temporary before main CB reclosing to avoid system damage that can be expected when the fault is permanent. To accomplish these goals, this paper proposes a ring-type dc bus-based microgrid system which has a segment controller between connected components.

LOW-VOLTAGE DC-BUS MICROGRID

Compared to high- voltage dc (HVDC) systems, the low-voltage dc (LVDC) system is a relatively new concept in electric power distribution. For small scale systems, LVDC microgrids have many advantages over traditional ac distribution systems. For both ac and dc microgrids, power-electronic converters are required to connect a variety of sources and loads to a common bus. Using a dc bus requires fewer stages of conversion [3]. Furthermore, the cables for the ac and dc power systems are chosen based upon the peak voltage of the system, and the power delivered by an AC system is based on the rms values, while the dc power is based on the constant peak voltage. Hence, the dc system can deliver √2 times that of an AC system with the same cable. And dc systems do not suffer from the skin effect. Therefore, the dc system can utilize the entire cable, thus decreasing losses [4].
Problems arise with dc microgrids when a system needs re-liable and versatile protection. AC systems have plenty of experience and standards when it comes to system protection. DC systems do not have either of these advantages. The switchgear in dc systems must be very robust in order to handle the dc arc that is created during the interruption of fault currents. The protection devices commercially available for low-voltage dc-bus systems are fuses and circuit breakers (CBs) [3]. Traditional ac CB mechanisms, which rely on the natural zero crossing of the ac current to open the circuit, are inadequate to interrupt dc currents. More important, the fault persists because the operating time of the CB increases. Allowing a fault current to persist on a microgrid bus could be catastrophic.
Because the microgrid systems need to be multi terminal, voltage source converters (VSCs) must be used to interface different subsystems to bus. When a fault occurs on the dc side of a VSC system interfacing the ac source, the insulatedgate bipolar transistors (IGBTs) lose control and the freewheeling diodes become a bridge rectifier feeding the fault. The challenge of protecting VSC systems is that the fault current must be detected and extinguished very quickly as the converter’s fault withstand rating is generally only twice the full-load rating [5].

FAULTS IN DC DISTRIBUTION SYSTEMS

A. Possible Faults

Two types of faults exist in dc systems: 1) line to line and 2) line to ground, which can be seen in Fig. 2. A line-to-line
image
fault occurs when a path between the positive and negative line is created, short circuiting them together. A line-to - ground fault occurs when either the positive or negative pole is short circuited to ground. The line-to -ground faults are the most common types of faults in industrial distribution systems [6]. VSCs may experience internal switch faults that can cause a line-to-line short circuit fault. This is a terminal fault for the device that cannot be cleared; in most cases, the device needs to be replaced. Hence, dc fuses would be a proper protection measure for this kind of fault. In AC systems, the AC-side CB will trip.

B. DC Fault Currents

When a fault occurs in a segment, the line current will split between load current and fault current
image
The magnitude of the fault current depends on the fault location and resistance of the fault current path. If the impedance of fault path is low (e.g., a line-to-ground fault with solid ground), the current polarity at the receiving end could be reversed, preventing the load from being supported at all. The fault current from the power source and bus capacitors can be given as follows:
image
where Vs is the line voltage, Rc and Lc are the equivalent resistance and inductance including source, line and ground component, and Rc and Ce are the equivalent series resistance (ESR) and capacitance of bus capacitors, respectively. The time constant of the dc fault current is quite small because the line resistance of the dc system is negligible compared to ac power systems that have high reactance in the line. The bus voltage will drop or even collapse, depending on the capacity of the power supply and energy-storage device in the bus, and the grounding impedance.

C. Fault Protection Techniques

Protection of dc systems has been done with dc protective switchgear as well as conventional ac devices, such as CBs and fuses. Although ac devices have advantages, such as low cost, maturity of technology, and shorter lead time, dc devices are a better option whenever possible. DC protective devices can interrupt constant current faster than their ac counterparts to isolate faulted lines and maintain the operation of unfaulted lines [2].

D. Fault-Location Techniques

Several methods have been investigated for locating faults in ac systems. Fault location can be determined using the computed reactance based on recorded fault current and voltage information at one terminal of a line [13]. Fundamental phasor information [14], phasor measurement unit (PMU) [15], and fault voltage sag [16] can be used as well. The traveling wave method computes the difference in time of arrival for a transient wavefront at two or more locations connected to a fault to locate the fault [17].
The existing dc fault-location techniques use rate of current rise, magnitude of current, current oscillation pattern [12], continuous wavelet transform [30], distributed parameter line model [19], iterative estimation using reference voltages [20], and artificial neural networks [18]. The accuracy of the aforementioned methods shows promise; however, the
image
dependence on two-terminal measurements restricts the practical uses. The instrumental aspects, such as the impact of sensor error and communication delay, have been investigated in [21]. Further-more, because the dc fault current rises so quickly, it may have to be interrupted before some useful information for the fault location can be obtained. Also, it may be difficult to extract the necessary information for fault location at the time of the fault, because the fault current is determined by other bus segments and components as well as fault impedance.

PROPOSED FAULT PROTECTION METHOD

Unlike other previously presented methods for dc systems [12], [22], the proposed protection method does not require a complete shutdown of the microgrid. Rather, only the affected section is isolated and de-energized. This is demonstrated with a ring-bus configuration for the dc bus, creating several zones of protection that can be defined using overlapping nodes and links within the bus. Each node consists of three CBs, and two CBs at each end of a bus segment form a link. This can be implemented for the positive and negative pole in bipolar systems. At each node, a probe power unit will be installed to locate the fault and test the bus for reclosing. A detailed diagram for the proposed system is shown in Fig. 3.The proposed protection scheme consists of the following components.

A. Fault Detection and Isolation

The master controller monitors the difference of two current readings of slave controllers in a segment
image
where i in and i out is the line current at each end of the bus segment. When the difference exceeds the threshold, the controller sends the appropriate commands to slave controllers so that the faulted segment can be separated from the system. Because the proposed system uses the differential relaying principle monitoring only the relative difference of input and output current of a segment, it can detect the fault on the bus regardless of fault current amplitude or power supply’s feeding capacity. Once the faulted segment has been isolated, the bus voltage will be restored and remainder of the system can continue to operate on the ring-type bus. Even with multiple faulted segments, the system can operate partially if the segments from some power sources to loads are intact. The possibility of the fault around the device connection point can be minimized if the segment controllers are installed as close to the connection point as possible.
image
The implementation of the proposed protection scheme is shown in Fig. 4, which shows the configuration of segment A in Fig. 3. Semiconductor based bidirectional switches S1 and D2 diodes are used for segment separation and fault current freewheeling, respectively. In normal operations, switches S1 are closed and diodes D2 are open. When a fault occurs, the master controller detects it using the current information from the slave controllers and opens S1 switches. Diodes D2 are conducting at the same time to form a freewheeling path for fault currents so that the S1 switches can open and the fault current can be extinguished through resistors. The segment controllers can detect the fault current of the line-to-ground fault (from point A or B to G) and line-to-line fault (from point A to B). A turnoff snubber circuit is included for S1 switches to limit the voltage overshoot due to the line inductance.
The line-to-ground fault is shown in Fig. 4. It can be seen that the fault current is isolated and extinguished in the freewheeling loop. The freewheeling path impedance determines the extinction rate of the fault current, which can be given as follows:
image
where Rf and Lf represent the resistance and inductance in the freewheeling path, respectively.
When a line-to-ground or a line-to-line fault occurs in the distribution line, the bus voltage collapse would not allow the load to ride through if the current is limited from the source because of insufficient capacity. This is especially true for the VSC-interfaced microgrid systems. Furthermore, the fault current needs to be extinguished as quickly as possible even if the system has sufficient current feeding capacity. Therefore, one of the best solutions would be to isolate the faulted line as soon as possible and continue operation with intact bus segments and subsystems. To achieve this, the segment controller needs to be capable of fast differential current detection and bus switch control. An automatic reclosing algorithm would be necessary for fault recovery and more robust operation [7].

B. Snubber Circuit

Snubber circuits are indispensable to protect the solid-state CBs from the voltage transient due to the inductance of the bus cable. It is more so especially in a loop-type bus where the line inductance exists on both sides of the CB unlike the point-to-point-type system. Although the fault current needs to be interrupted as quickly as possible, the high di/dt could make the transient voltage catastrophically high for the solid-state switches. There are a couple of snubber circuit topologies to suppress the overvoltage at turn-off due to line inductance, such as decoupling capacitor, discharge restricted decoupling capacitor, discharge-charge-type RCD snubber, and discharge-suppressing-type RCD snubber [8]. It has been reported that the decoupling capacitor has low losses but also oscillation issues and RCD snubbers have higher losses but no oscillation problem and good for higher current applications [9]. Since the solid-state CBs do not switch in high frequency, charge-discharge-type RCD snubber has been chosen for better voltage suppression performance.

C. Fault Segment Modelling With the Probe Power Unit

Once the faulted bus segment is isolated, a second-order RLC circuit can be formed with the probe power unit through the fault path as shown in the equivalent circuit shown in Fig. 8. When the switch Sp in the probe power unit is closed, the dynamics of the probe current can be expressed as
image
image
The equivalent resistance and inductance of the fault path will be given as the sum of line and fault resistances and the line and probe inductance, respectively as shown in Fig. 5. The line leakage capacitance can be neglected because the capacitance of the probe capacitor is significantly larger. The probe capacitor and probe inductance will determine the frequency of the probe current. Because of the large R/L ratio of power cable [23], the probe current will decay too fast without probe inductance. Hence, the fault circuit components, including the probing unit components, are given as
image
image
image
where R1 and L1 are the line resistance and inductance to fault location, which are defined as
image
image
image
Since there is no driving voltage in the circuit except the initial probe capacitor voltage, the probe current i can be given as a zero-input response of the RLC circuit
image
image
image
image
image
image
image

D. Identification of Fault Location

The underdamped response frequency of the probe current is a function of natural frequency and damping factor. If the damping factor is small enough (controllable with the probe capacitor and inductor), the damped response frequency becomes very close to the natural frequency, which is function of inductance of the faulted segment L1, probe inductance LP, and probe capacitance CP.Because the capacitance and inductance of the probe circuit (CP and LP) and unit inductance of the line Lu are known parameters, the distance to the fault location can be readily calculated from the probe current frequency fip using (17)
image
image
image
image
image
The damped resonance frequency ������can be obtained from sampled current data using a fast Fourier transform (FFT) algorithm.

SIMULATION RESULT

A computer simulation has been performed for a microgrid system that consists of three typical energy devices: a source, a load, and energy storage. They are connected as shown in Fig. 7. Stiff dc power sources are assumed so that a constant fault current is fed by the sources without a voltage drop. A 240V bipolar dc bus with 200m bus segments and a fault at the middle (100m) of the bus is simulated. Simulation parameters can be found in Table I.
image
image
image
A positive line-to-ground fault in the middle of the bus segment A is simulated at 1ms. Fig. 8 shows the source and load-side current of a line-to-ground fault with and without protection. It can be seen that the current from source increased to 180 A after 0.5 msec. The fault current magnitude depends on the impedance of the fault path. The currents at each end of the segment which had been identical before faultshow clear difference after fault. Line-to- line fault current will be higher be-cause there is no resistance to limit it. Therefore, fast detection and isolation are critical.It has been assumed in the simulation that the segment controllers can detect it and open/close solid-state CBs in 250 s. considering the speed of current microcontrollers and switching devices, fast interruption in this speed range isfeasible. Fig. 8.And Fig. 9.also shows that the fault currents are extinguished when the faulted segment is separated.
image
Fig. 10 shows the voltage transient across the solid-state CB S11 without and with the snubber circuits, respectively. It also shows the fault extinction in the freewheeling path. The voltage transient at turnoff due to the line inductance and high di/dt can be very high and it can easily damage the solid-state switch. It can also be seen that the voltage transient is suppressed by a snubber circuit at a tolerable level.
Fig. 11 shows the voltage across the load. The ground fault pulls the positive pole voltage to zero, and the bipolar dc bus will experience a voltage offset on the faulted pole. However, the load voltage is quickly restored after the faulted segment has been separated.
Fig. 12 shows the current in the bus segment C and voltage of bus segment B and C and current in freewheeling path. The bus segment C experience the ground fault current and voltage sag is experience in bus segment B and C.
After the faulted segment is separated by IEDs, it is tested by the probe power unit to confirm the fault status and location. The capacitance and inductance value of the probe power unit components can be computed using 27 F and657 μH, respectively, with 0.025 damping factor and 50-ms probing period. The probe current decays as designed and clearly shows the oscillation frequency . For the fault at 100m on the bus segment, the frequency is 718.95 Hz. The FFT analysis extracts the frequency as 719.0 Hz and the fault location was identified using (17) with 0.02% error (100.02m).
image
The protective devices in bus segments B and C have been omitted in this simulation because the proposed protectivescheme that detects the difference in net current flow will not be triggered if there is no fault in the bus. This can be verified by the currents flowing into and out of the intact bus segment C shown in Fig. 12. Even with the transient caused by the fault on the bus segment A, the incoming and outgoing currents of segment C are identical. The proposed scheme that detects the current difference is robust to common-mode noise and transient due to a fault.

CONCLUSION

A fault detection, isolation, and location scheme for the dc microgrid system has been presented in this paper. The proposed protection scheme consists of IEDs which are capable of detecting fault current in the bus segment and isolating the segment to avoid the entire system shutdown. A ring bus based microgrid system with IEDs, has been used. For the separated faulted segment, a fault-location algorithm using a probe power unit without having to reclose the main CBs has also been presented. This bus probing method can ensure the proper line status before reclosing and, hence, improves the system reliability and mean time between failure (MTBF) of protective gear. Furthermore, it can be readily applied to ac power systems to eliminate the issues caused by reclosing failure, as well as to identify the fault location. Successful performance of fault detection, isolation, and location have been shown using computer simulations.

References