Keywords
|
Canonical Switching Cell, Power Factor, THD, Brushless DC Motor, IEC 61000-3-2. |
INTRODUCTION
|
In recent years the BLDC motor is widely used in many low and medium power applications, because of its high energy density, high torque /inertia ratio, high efficiency and low maintenance due to the absence of the commutator and brush assembly. The BLDC motors are used in household appliances like washing machine, water pumping and air conditioning etc. and also in industries like robotics and industrial tools and motion control equipment. In the BLDC motor the commutation is done by using the electronic commutation; it involves hall-effect sensors to sense the rotor position and energizes the corresponding phase windings in the proper sequence by using the voltage source inverter (VSI) [1]. In the conventional scheme the BLDC motor drive system is fed by a diode bridge rectifier (DBR) which draws a current from ac mains with higher harmonic levels, also the power factor has been affected and it is not satisfies the PQ standard IEC 61000-3-2, so the power factor correction (PFC) is required for attaining good PQ parameter. The boost converter is widely used in the BLDC motor drives, in which the DC link voltage is maintained constant and the speed is controlled by controlling the PWM pulses of the VSI. This system has a drawback for the higher amount of the switching losses in the VSI switches due to higher level of the switching frequency at the inverter switches and the higher current levels [2-5]. In the sepic and cuk converter fed BLDC motor drive the speed of the motor is controlled by controlling the DC link voltage, hence the switching losses associated with the VSI switches are reduced, but it has a problem of using two sensors, which increases the system cost [6-7].The CSC converter based system presents a single voltage sensor based BLDC motor drive system, which is a cost effective solution of the low power applications. |
CANONICAL SWITCHING CELL CONVERTER FED BLDC MOTOR DRIVE
|
Fig. 1 shows the CSC converter fed BLDC motor drive consists of the front end CSC converter. It is operated at low switching frequency, so that the near unity power factor is achieved at ac mains. The speed of the BLDC motor is controlled by controlling the DC link voltage of the CSC converter. Moreover low frequency operation of VSI reduces the switching losses. The system shown in Fig. 1 gives a near unity power factor at ac mains for a wide range of the speed and the supply voltage. |
Fig. 1 Block diagram of the Canonical Switching Cell converter fed BLDC motor drive |
The CSC [8] converter is operated in discontinuous inductor current mode (DICM) Fig. 2 shows the discontinuous inductor current. The converter is operated in three differnt modes [8] in every switching period, these as follows: |
Mode I: In this mode the CSC converter switch is ON, the inductor charges the input current and the capacitor C1 discharges the energy to the DC link capacitor, the DC link capacitor is charging as well as supplies a energy to the BLDC motor drive, so the DC link capacitor is fixes to the higher value for supplying a continuous energy to the motor drive. |
Mode II: In this mode the CSC converter switch is going into OFF state, then the inductor Li discharges the stored energy to the DC link capacitor through diode D. In that time the capacitor C1 charges the DC voltage comes from the diode bridge rectifier (DBR). |
Mode III: This mode starts when the inductor current is going to be zero, automatically a diode D goes into the reverse biased condition, the capacitor C1 is continues to charging, then the DC link capacitor discharges the energy to the VSI fed BLDC motor drive. |
DESIGN OF CANONICAL SWITCHING CELL CONVERTER AND CONTROLLER
|
The designing of the CSC converter depends on the rating of the motor to be interfaced with it, the 950 W of the CSC converter is designed for the 850 W BLDC motor considering the losses in the system. The design equations are given through (1) – (6). The voltage at the output of the DBR is as follows, |
|
where Vs is the input supply voltage. A duty ratio of the converter is as follows, |
|
where Vdcn is the DC link voltage. The critical value of the inductance is |
|
The inductor value of the CSC converter is taken as follows for support a DCIM mode is |
|
The value of the capacitor C1 is chosen as follows, |
|
The design of the DC link capacitor as follows, |
|
Where fs is the switching frequency, Rload is the resistance of the motor and ΔVdc is the ripple in the DC link voltage. The determined values of the CSC converter parameters for 850 W motor are L=40 μH, C1=379 μF and Cd=2100.58 μF. These values are designed for the supply voltage (Vs) of 230 V, range of the DC link voltage of 30-90 V and the switching frequency (fs) is 4 kHZ. |
The CSC converter is controlled by using the PWM signals to the converter switch, which maintains the desired voltage level across the DC link capacitor. The DC link voltage is measured using single voltage sensor (Vdc) and the reference DC link voltage is generated as follows, |
|
where kb is the motor voltage constant and ω* is the reference speed of the motor. The reference DC link voltage is compared with the measured DC link voltage and gives a error signal Ve(t) to the proportional integral (PI) controller as, |
|
The PI controller generates a controlled signal Vc(t) as, |
|
Where Kp and Ki are the gain values of PI controller, The initial values of the controller are obtained using Ziegler- Nichols tuning method and then fine-tuned. The obtained values are Kp = 0.9 and KI = 27.9792 respectively. This controlled signal is given to the PWM modulator to produce proper gating signals to the converter. The proper operation of the BLDC motor is attained only when the electronic commutation works properly. The electronic commutation is to switch the DC voltage to proper phase winding of the motor, based on the rotor position signal. The rotor position signals are obtained using Hall Effect sensors, based on this position signals the corresponding phase windings to be energized which is shown in Table 1. The equivalent circuit of the BLDC motor comprises of resistance (Rn), inductance (Ln), back emf (En) in each phase and its design is discussed in [9-10]. |
Table 1. 120° commutation table of the BLDC motor |
SIMULATION RESULTS AND DISCUSSION
|
The performance of the system shown in Fig. 1 with designed parameters discussed in Section III is analyzed under steady state and dynamic condition. The performance parameters taken into considerations are the supply voltage (Vs), supply current (is), DC link voltage (Vdc), motor speed (ω), electromagnetic torque (Te ), motor phase current (ia), voltage and current stress of the switch (VSW, iSW) and PQ terms like supply current THD, displacement power factor (DPF), power factor (PF). Fig.2 shows the MatLab-Simulink model of the system and the motor parameters are listed in Table 2. |
Fig. 2MatLab-Simulinkmodel of the CSC converter fed BLDC motor drive |
Table 2. BLDC motor parameters |
STEADY STATE RESPONSES OF THE CANONICAL SWITCHING CELL CONVERTER FED BLDC MOTOR DRIVE |
Fig. 3 shows the steady state responses of the drive. BLDC motor is loaded at the rated load torque of 1 N-m, supply voltage of 220 V. A sinusoidal current is drawn at AC mains with the DC link voltage of 60 V and it is in-phase with the supply voltage gives the near unity power factor. The voltage and current stress of the proposed converter switch is obtained as 400 V and 7 A. |
Fig. 3 Steady state responses of the CSC converter fed BLDC motor drive |
The THD of the supply currents under steady state with different DC link bus voltage of 30 V and 60 V is obtained as 14.78% and 6.67%, this are the acceptable range by referring the PQ standard IEC 61000-3-2 [11], the corresponding harmonic spectra with the supply current are shown in Fig. 4 and Fig. 5 respectively. It is observed that the THD of the supply current is improved at higher DC link voltage levels. |
Fig. 4 Supply current and its THD window of the proposed system at the DC link voltage of 30 V |
Fig. 5 Supply current and its THD window of the system at the DC link voltage of 60 V |
DYNAMIC RESPONSES OF THE CANONICAL SWITCHING CELL CONVERTER FED BLDC MOTOR DRIVE |
To analyse the dynamic response of the system, dynamics are introduced in terms of step change in DC link voltage, change in the motor loading, and change in the supply voltage. |
PERFORMANCES UNDER CHANGE IN DC LINK VOLTAGE |
Fig. 6 shows the responses of the proposed BLDC motor drive for the change in DC link voltage with the motor loaded at the rated condition and the supply voltage of 220 V. The DC link voltage is changed from 30 V to 60 V at the time of 1 s and in the motor speed the smooth transition has been takes place from the speed of 330 rpm to 1000 rpm with minimum overshoot in the motor speed. |
Fig. 6 Dynamic responses of the drive under the change in DC link voltage |
The starting inrush current and the transition current also been reduced for both supply and motor phase current within the permissible level, these values has been tabulated in Table 3. This table comprises of the THD, DPF and PF for different values of DC link voltages, these values are the acceptable ranges by referring the PQ standard IEC 61000-3- 2. |
Table 3. Performance parameters of the system under the change in the DC link voltage |
Fig. 7shows the harmonic spectra with the corresponding supply current under the condition for change in DC link voltage. Fig. 8 shows the plot for THD and PF under different values of the DC link voltage Vdc. |
Fig. 7 Supply current and its THD window of the system under dynamic conditon for the change in DC link voltage |
Fig. 8Performance plot under the change in the DC link voltage |
The THD under this condition is 6.40 % is obtained and it is acceptable range by referring the PQ standard IEC 61000- 3-2. |
PERFORMANCE UNDER CHANGE IN SUPPLY VOLTAGE |
Fig. 9shows the performances of the motor drive under the condition for variations in the magnitude of the supply voltage from 190 V to 240 V the current drawn from the supply is reduced lower voltage level to the higher voltage level. A small disturbance occurs in the motor speed, DC link voltage, motor phase current and motor torque at the time of the supply voltage changes, but it recovers at very short time using PI controller. In this condition the power factor is obtained about 5.91 % which is an acceptable limit by referring to the PQ standard IEC 61000-3-2. |
Fig. 9 Dynamic responses of the drive under the change in supply voltage |
Fig. 10 shows the supply current and its harmonic spectra for change in the supply voltage, it gives the acceptable THD value for supply current about 5.91 % as per the PQ standard of IEC 61000-3-2. Table 3 shows the Performance of the proposed drive in terms of the supply current THD , power factor, displacement power factor and motor speed for varying the supply voltage from 150 V to 240 V and corresponding plot is shown in Fig. 11. |
Fig. 10 Supply current and its THD window of the system under dynamic conditon for the change in supply voltage |
Table 3. Performance parameters of the system under the change in the supply voltage |
Fig. 11 Performance plot under the change in the supply voltage |
PERFORMANCE UNDER THE CHANGE IN MOTOR LOADING CONDITION |
`Fig. 12 shows the performances of the motor drive under the condition for variations in the motor loading condition. Initially the motor starts at the load torque of 0.5 N-m and at the time of 1 s the load torque is changed to 1 N-m, the corresponding speed is changed from 1200 rpm to 1000 rpm. The supply and motor currents has been changed smoothly under these conditions |
Fig. 12 Dynamic responses of the proposed drive under the change in motor load |
Fig. 13 shows the harmonic spectra and the supply current for the change in motor load condition. The supply current THD has been obtained about 6.07 %.Apart from the above analyses, the voltage and current stresses of the CSC converter switch is tested under different loading conditions and shown in Table 4. |
Fig. 13 Supply current and its THD window of the system under dynamic conditon for the change in motor load |
|
Table 4. Voltage and current stresses of the CSC converter switch at different motor loading |
Table shows that the voltage stress of the switching device is about 400 V at any loading condition. The maximum current stress of the switching device is 7.8 A at 100 % loading. |
CONCLUSION
|
In this paper the steady state and dynamic conditions were checked for CSC converter fed BLDC motor drive for the improvement in terms of power quality. This converter claims the major advantages of using one sensor, low THD high PF at AC mains, low switching losses due to low frequency operation. The supply current THD was obtained below 7% under the wide range of the motor speed and the supply voltage where those values are recommended by the PQ standard IEC 61000-3-2, hence it is well suited for low power applications. This work can be further improved by using advanced controllers. |
References
|
- R. Krishnan, “Electric Motor Drives: Analysis, Modeling and Control”, Prentice Hall Inc., New Jersey,2001.
- Mehdi Narimani and Gerry Moschopoulos., "A New Single-Phase Single-Stage Three-Level Power Factor Correction AC–DC Converter,”IEEE Transactions on Power Electronics, Vol. 27, No. 6, pp. 2888-2899, June 2012
- ShiguoLuo, Wenkai Wu and IssaBataresh, “Flyboost Power Factor Correction Cell and a New Family of Single-Stage AC/DC Converters,"IEEE Trans. Power Electronics, Vol. 20, No. 1, pp. 25-34, Jan. 2005.
- Juan Paulo Robles Balestero, “Power Factor Correction Boost Converter Based on the Three-State Switching Cell,” IEEE Transactions onIndustrial Electronics, Vol. 59, No. 3, pp. 1565-1577, March 2012.
- S. H. A. Kaholi, M. Mounsouri, J. Selvaraj and N. B. A. Rahim, “A Hybrid Adaptive Neural-Fuzzy Tuned P.I. Controller BasedUnidirectional Boost P.F.C. Converter Feeds B.L.D.C. Drive,” 4thPower Electronics, Drive Systems & Technologies Conference, pp. 176-181,Feb. 2013.
- Abbas A. Fardoun, Esam H Ismail, Ahmad J Sabzali and Mustafa A Al-Saffar, “New Efficient Bridgeless Cuk Rectifiers for PFCApplications,” IEEE Transactions on Power Electronics, Vol. 27, No. 7, pp. 3292-3301, July 2012.
- Sanjeev Singh and Bhim Singh., "Voltage Controlled PFC SEPIC Converter fed PMBLDCM Drive for an Air-Conditioner," PowerElectronics, Drives and Energy Systems (PEDES) & 2010 Power India, 2010 Joint International Conference, pp. 1-6, Dec. 2010.
- VashistBist and Bhim Singh, “A PFC-Based BLDC Motor Drive Using a Canonical Switching Cell Converter,”IEEE Transactions onIndustrial Informatics, Vol. 10, No. 2, pp. 1207-1215, May 2014.
- U. Neethu and V. R. Jisha, “Speed Control of Brushless DC Motor: A Comparative Study,” IEEE conf. Power Electron. Drives and EnergySystems, pp. 1-5, Dec. 2012.
- AnandSathyan, Nikola Milivojevic, Young-Joo Lee, Mahesh Krishnamurthy and Ali Emadi, “An FPGA-Based Novel Digital PWM ControlScheme for BLDC Motor Drives,” Vol. 56, No. 8, pp. 3040-3049, Aug 2009.
- Limits for Harmonic Current Emissions (Equipment Input Current ≤16 A Per Phase), Int. Std. IEC 61000-3-2, 2000.
- www.mathworks.com
|