ISSN ONLINE(2278-8875) PRINT (2320-3765)

All submissions of the EM system will be redirected to Online Manuscript Submission System. Authors are requested to submit articles directly to Online Manuscript Submission System of respective journal.

Research Article Open Access

TRANSIENT TORSIONAL TORQUE STRESSES REDUCTION ON TURBINEGENERATOR SHAFTS BY SIMULTANEOUS AC-DC POWER TRANSMISSION

Abstract

This research paper investigates the effects of line faults, line de-energization and line re-energization on the transient torsional stresses of steam turbine-generator (T-G) units in simultaneous AC-DC transmission system. The concept of damping the transient torsional torque stresses excited due to line faults by utilizing fast controllability and modulation of dc component in simultaneous AC-DC power transmission is also demonstrated. The studies are conducted on a simultaneous AC-DC line system which connects T-G set to a large ac system. For the purpose of comparison the simultaneous AC-DC power transmission system is replaced by an equivalent conventional AC system and performances are evaluated. The studies conclude that transient shaft stresses as a result of simultaneous AC-DC line fault and its subsequent switching events are significantly less severe than those of conventional AC line faults and subsequent switching. PSCAD/EMTDC software is used to carry out for simulation studies.

H.Rahman, B.H.Khan

To read the full article Download Full Article | Visit Full Article